We recently installed solar panels and battery.
AGL shows the usage of grid electricity
While my elekeeper app shows that we did not use any electricity from the grid
Not sure why this is happening. AGL suppose to reconfigure our intelligent meter (this fellar from intellihub installed isolator), and I can monitor my app, that we not taking any from the grid.
Can somebody from the community suggest what is wrong?
Odd how it is only on those 2 days, the 1st and 4th of October. Do you have an electric HWS ? If so, it's likely this is on CL (controlled load) still, and that is metered separately, solar and battery will not have an effect on that. It is odd that you'd expect that to come on every day though, not just the 2 days out of 5 shown.
When you click on the days in that graph, does it break down the time of day for usage, and if so is that in solar soak and / or old off peak times ? If it could be the HWS, then you will see controlled load on your plan info.
I did a simple mod to fix this and happy to share if you let me know about the HW possibility.
HWS - Hot Water System? No we don't, we have gaz heater. I do notice though, that in the morning when I check battery SOC status, it varies between 70 and 95%%, which tells me we use battery electricity or grid. And nothing changed on electricity use. Thank you for your kind response
I can understand why that would be confusing when your monitoring app and the usage shown by AGL don't appear to match.
There can be a few reasons for differences between third-party solar monitoring apps and the data that comes through your electricity meter.
Just for information, AGL receives usage data directly from your electricity meter. The meter records electricity imported from the grid and electricity exported back to the grid. It doesn't have visibility of how much solar energy your system generates, how much solar energy is used directly in your home, or how much energy is stored in or discharged from your battery. Those details are typically captured by your inverter or energy monitoring app.
Because of this, it's possible for the figures shown in AGL and your energy monitoring app to differ, as they may be reporting on different types of energy flows. If you're concerned that the meter configuration isn't correct following your solar and battery installation, it's worth contacting AGL so the metering setup can be reviewed. https://www.agl.com.au/help-support/contact-us#
You need to look at those individual days and see when you were consuming power from the grid.
The other factor you need to consider is that AGL is using your reported usage which is a proven process..
Your solar app may not be configured correctly, the taps may not be on the correct wires.
You also have not noticed that you are consuming power from the grid every day.
I had batteries installed on the 3rd Sept 26 and had to shut them down because the app indicated that I was discharging my batteries back to the grid. Reported this to the company that I purchased the batteries from and had to turn off the batteries.
I diagnosed the issue myself and found that the CT taps were connected to wrong wires. I switched the plugs over myself and have no issues since (except trying to get someone to fix the wiring, which took 29 days).
Now I have still consumed a whole 1.6kw of grid power in the 22 days of the current billing cycle. This I can see on the app and appears to be an issue where it momentarily draws power from the grid, this has cost me $0.54 so far.
DATE
NMI
Daily Total
Peak 00:00> 01:00
Peak 06:00> 10:00
Peak 15:00> 00:00
Shoulder 10:00> 15:00
Off Peak 01:00> 06:00
Solar 2Grid
20260919
E1
0.001
0
0
0.001
0
0
23.829
20260920
E1
0.038
0
0.015
0.003
0.02
0
18.238
20260921
E1
0.037
0
0.003
0
0.034
0
12.113
20260922
E1
0.025
0
0
0.016
0.009
0
19.146
20260923
E1
0.016
0
0.001
0.013
0.002
0
22.273
20260924
E1
0.044
0
0.008
0.01
0.026
0
4.59
20260925
E1
0.059
0
0.021
0.003
0.035
0
14.831
20260926
E1
0.031
0
0.005
0.006
0.013
0.007
0.915
20260927
E1
0.056
0
0.004
0.018
0.03
0.004
14.823
20260928
E1
0.028
0
0.003
0.02
0.004
0.001
16.034
20260929
E1
0.064
0
0.013
0.001
0.05
0
10.606
20260930
E1
0.041
0
0.004
0.003
0.032
0.002
0.989
20261001
E1
0.592
0
0.015
0.002
0.575
0
0.961
20261002
E1
0.088
0
0.027
0.021
0.04
0
0.889
20261003
E1
0.104
0
0.012
0.029
0.063
0
6.987
20261004
E1
0.021
0
0.002
0.008
0.011
0
0.919
20261005
E1
0.099
0
0.001
0.013
0.084
0.001
10.577
20261006
E1
0.085
0
0.026
0.009
0.05
0
11.327
20261007
E1
0.014
0
0.001
0.01
0
0.003
23.796
20261008
E1
0.024
0
0.01
0.012
0.002
0
19.462
20261009
E1
0.016
0
0.008
0.004
0.004
0
0.945
20261010
E1
0.118
0
0.024
0.003
0.091
0
11.612
Total:
E1
1.601
0
0.203
0.205
1.175
0.018
245.862
It is interesting to note that this only occurs when I am generating solar, over the full 90 day billing cycle this will cost me $2.22 (inc GST).
I am in the process of trying to get this resolved by the Battery Supplier.
By the way you are about 35kms south of my location and you can see that on both of these days (1st / 4th) I manage to fully charge my batteries but solar output less than 1kWh into the grid also I consumed 33% of my grid usage so far.
I have attached my screenshot from my app for the 1st Oct. You can see inconsistent reporting here. The graph shows that I had a input of 3kW at around 1400 while the energy balance show an import of .85kWh for the day. However, we know that my Smart Meter only reported .592kwh but the AGL daily report for 1st Oct shows .53kWh for 13:00 (by the way the times shown on that display are in correct the first time should be 1 am and the last time should be midnight on the 1st).
The NEM format file for that day shows .53kWh for the period 13:30 to 14:00. If you wish to discuss this further send me a private message.
Lester
+21 more
Powerhouse
•
23 days ago
Odd how it is only on those 2 days, the 1st and 4th of October.
Do you have an electric HWS ?
If so, it's likely this is on CL (controlled load) still, and that is metered separately, solar and battery will not have an effect on that.
It is odd that you'd expect that to come on every day though, not just the 2 days out of 5 shown.
When you click on the days in that graph, does it break down the time of day for usage, and if so is that in solar soak and / or old off peak times ?
If it could be the HWS, then you will see controlled load on your plan info.
I did a simple mod to fix this and happy to share if you let me know about the HW possibility.
1
0
kwaka9
+1 more
Switched-on
•
22 days ago
Worth asking AGL for a please explain.
Don’t know why AGL can’t show how much solar you’ve generated that you have used.
They would have to know the data through your smart meter to calculate how much you drew from the grid, as per your discrepancy.
1
0
NeilC
+22 more
Powerhouse
•
18 days ago
@HoldenHillSolar
You need to look at those individual days and see when you were consuming power from the grid.
The other factor you need to consider is that AGL is using your reported usage which is a proven process..
Your solar app may not be configured correctly, the taps may not be on the correct wires.
You also have not noticed that you are consuming power from the grid every day.
I had batteries installed on the 3rd Sept 26 and had to shut them down because the app indicated that I was discharging my batteries back to the grid. Reported this to the company that I purchased the batteries from and had to turn off the batteries.
I diagnosed the issue myself and found that the CT taps were connected to wrong wires. I switched the plugs over myself and have no issues since (except trying to get someone to fix the wiring, which took 29 days).
Now I have still consumed a whole 1.6kw of grid power in the 22 days of the current billing cycle. This I can see on the app and appears to be an issue where it momentarily draws power from the grid, this has cost me $0.54 so far.
It is interesting to note that this only occurs when I am generating solar, over the full 90 day billing cycle this will cost me $2.22 (inc GST).
I am in the process of trying to get this resolved by the Battery Supplier.
By the way you are about 35kms south of my location and you can see that on both of these days (1st / 4th) I manage to fully charge my batteries but solar output less than 1kWh into the grid also I consumed 33% of my grid usage so far.
I have attached my screenshot from my app for the 1st Oct. You can see inconsistent reporting here. The graph shows that I had a input of 3kW at around 1400 while the energy balance show an import of .85kWh for the day. However, we know that my Smart Meter only reported .592kwh but the AGL daily report for 1st Oct shows .53kWh for 13:00 (by the way the times shown on that display are in correct the first time should be 1 am and the last time should be midnight on the 1st).
The NEM format file for that day shows .53kWh for the period 13:30 to 14:00. If you wish to discuss this further send me a private message.